NOTE 10: ID-200 WASTE HYDROCARBON & SLOP OIL TANK SYSTEMS

INTRODUCTION

Many manufacturing processes produce hydrocarbon waste that contain varying amounts of water. Some of these industries are:

  • Refining
  • Chemical Manufacturing
  • Steel
  • Metal Finishing
  • Pharmaceutical

This waste material is usually collected in waste tanks (or slop tanks) and treated on a batch basis. The goal of the treatment is to break hydrocarbon and water emulsions to the free phase hydrocarbon and water, then remove all the water possible from the hydrocarbon. The recovered water is usually sent to waste water treatment or other internal recycling facilities. In most cases, the recovered hydrocarbon is a waste product with little or no value. However, refineries are able to recycle recovered slop oil into the desalter crude feed or coker feed.

In the treatment of waste oil, the adjustable sensitivity of the AGAR ID-201 Interface Detector is used to perform three functions in a waste or slop tank:

  • Automatic Dewatering Control
  • Emulsion Build-Up Monitoring
  • Automatic Outlet Oil Quality Control

Please refer to the wash/slop tank application drawing below.

1. Automatic Dewatering Control

Probe #1 is inserted approximately 1-3 feet from the bottom of the tank to control the water dump valve. It should be inserted horizontally for ON-OFF control, or at a 45o angle for modulating control. The set point should be set at approximately 80% water. This will force the emulsion to build above the probe and will virtually eliminate the dumping of free-phase hydrocarbons with the effluent water.

2. Emulsion Build-Up Monitoring

Probes #2, #3, and #4 monitor the water content in the hydrocarbon emulsions at various levels in the tank. This information is used to determine chemical injection or heat treatment requirements.

3. Automatic Outlet Oil Quality Control

Probe #5 is inserted about three feet below the dry oil outlet to monitor the quality of the oil leaving the tank. The probe has a 4-20 mA output corresponding to water content of the oil before discharge and an alarm relay that can be used as an override to handle the build-up of untreatable emulsion.

Slop Oil

Wash/Slop Tank Application Drawing